AGC Flatglass Pyrobel 53, 53N EG
AGC Flatglass · evidence reference CF377 (Warringtonfire Certifire, stated validity to 20 Jun 2029)
Within stated validity to 20 Jun 2029; issuer status still requires checking
This glass can achieve different fire ratings depending on how it is used — internal or external, door or screen, single or double-glazed unit, and the framing system. Each record below must be checked against the current certificate, test regime and complete framing, seals, fixings, installation and exposure. Only explicitly reviewed mappings carry review provenance; other extracted data remains unverified.
Request a quote for this glass
Give us your size and contact details and verified local suppliers will quote — no account needed, just an email to confirm.
Certified options for this glass
Check recorded size bounds and outstanding evidence
A size fit is only one part of qualification. The complete framing, seals, fixings, exposure and current certificate must be checked. No rotation or interpolation between tabulated pairs is assumed.
System verification required
Test regime / source mapping unverified · numeric integrity/insulation minutes do not automatically establish EN 13501 E/EW/EI.
Within stated validity to 20 Jun 2029; issuer status still requires checking
Screen
Steel
Single
External
3.67 m² max area
Confirm the cited system's width, height, area, orientation and any dimension graph; do not assume rotation or interpolation.
- Hilti 100 HT – 10 mm dieameterx112mm
- Steel profile – Forster Fuego 110 mm by 55 mm
- Clipped beads – 25 mm by 25 mm
- Setting block – 70 mm by 53 mm x 5 mm
- Steel screw – 4 mm diameter, 16 mm long
- Ceramic paper – 20 mm by 5 mm
- Setting block – 100 mm by 110 mm by 15 mm
- Silicone – Dow Corning Firestop 700
- Intumescent Strip – Palusol 65 mm by 2 mm
- Pyrobel 53N & 53N EG
Understanding the grades
Integrity for the classified duration. It does not establish radiation control or insulation.
The complete system and classification report determine E performance.
Integrity plus a radiation limit for the classified duration. EW is distinct from E and from EI.
Check radiation performance in the system classification report.
Integrity plus insulation for the classified duration. A BS 476 integrity/insulation pair alone is not an EN 13501 EI classification.
Specify class and minutes from the project fire strategy.
Manufacturer location/exposure terminology, separate from fire-resistance class. Confirm the specific glass, system and installation conditions.
Internal/external suitability cannot be inferred from the letters E, EW or EI.