Fire-rated glass

Review candidate fire-glass systems and their evidence. The performance depends on internal or external use, door / screen / DGU application, frame material and exact system, size, orientation and installation. Refine below, then verify the current certificate and all construction conditions. Records without reviewed source mappings remain explicitly unverified. BS 476 numeric pairs are not automatically EN 13501 E/EW/EI classifications. Browse by manufacturer ↓

Product guide

Fire glass for a specified glazing system

Capture the required classification, duration, frame and application so a specialist can quote a compatible tested assembly.

A fully framed internal glazed screen and door concept.
AI-generated illustration. Appearance varies by specification; this is not an exact product sample.

Fire-rated glass, fire-resistant glazing and glazed fire doors or screens

Fire-resistant glass must be specified as part of a compatible tested glazing system. The glass, frame, beads, seals and fixings all contribute to the assembly. Start with the project fire specification and identify the required application, classification and duration.

E, EW and EI describe different protection criteria. Integrity, radiation control and insulation are not interchangeable descriptions. A time period on its own does not tell the supplier which performance is needed or whether a particular size and frame are covered by the evidence.

Give the supplier the door or screen arrangement, orientation, installation location and exact system details. Replacement glass should be checked against current evidence for the full assembly. Neither a generic product name nor a photograph establishes a valid fire classification.

Fire glass for a specified glazing system for your project

Common enquiry briefs include door vision panel, internal screen, external window, roof or overhead glazing. Describe the intended use and the supporting construction so the supplier can assess the complete specification. Different applications can need different glass processing, fixings and installation details.

Start with the fire strategy

The classification and duration come from the project requirements, then the specialist checks a compatible glazing system.

The frame is part of the answer

A glass rating cannot be transferred to a different frame, seal, installation or untested size.

What to include in a made-to-measure quote

Compare quotes using the same dimensions, quantities, finish, glass construction and installation scope. If you have a drawing or an existing specification, include its reference and identify which details still need advice.

  • Required classification: Use the project fire specification. E, EW and EI describe different protection criteria.
  • Required duration: A duration is a project requirement, not approval of this configuration.
  • Frame / glazing system: Glass, frame, beads, seals and fixings must be compatible.
  • Exposure: Internal and external products and overhead systems are not interchangeable.

Cut-to-size dimensions, edges and fabrication

Measure the finished glass only when the fitting allowances and support details are known. Otherwise identify the opening or existing panel you measured and request a survey. Give each different size its own basket line, with its quantity and drawing reference.

Holes, cut-outs, shaped edges and interfaces with hardware should be settled before manufacture. The finished glass construction and any coatings must suit the intended environment. A screen preview or concept photograph cannot replace a sample, survey or product-specific installation drawing.

Supplier checks before manufacture

  • Supplier must verify the entire tested assembly and allowed pane dimensions.
  • Do not replace fire glass on thickness or appearance alone.

Requesting comparable glass quotes

Save the choices you know and ask for help with the rest. The quote basket records a specification request rather than placing a manufacturing order. A firm quote needs an agreed final build, dimensions, delivery arrangements and any installation or design work.

When comparing proposals, check that glass-only supply and supply with fitting cover the same scope. Ask who provides measurement, drawings, supports, compatible hardware, lifting access and finishing work. Keep the final approved specification with the order.

Sources and further reading

Need a quote for fire-rated glass?

Open any glass below, enter your size and contact details, and verified local suppliers will quote — no account needed.

Browse models ↓
E

Integrity for the classified duration. It does not establish radiation control or insulation.

The complete system and classification report determine E performance.

EW

Integrity plus a radiation limit for the classified duration. EW is distinct from E and from EI.

Check radiation performance in the system classification report.

EI

Integrity plus insulation for the classified duration. A BS 476 integrity/insulation pair alone is not an EN 13501 EI classification.

Specify class and minutes from the project fire strategy.

INT / EXT / EG

Manufacturer location/exposure terminology, separate from fire-resistance class. Confirm the specific glass, system and installation conditions.

Internal/external suitability cannot be inferred from the letters E, EW or EI.

Glass selector

Find candidate systems

These filters screen recorded evidence. Your project specialist must verify the complete frame, seals, fixings, aperture and fire exposure. A material name or area alone cannot approve a system.

Examples and guidanceExact framing / glazing system

Material alone is insufficient. Supply system, seals and supporting assembly; comparison remains a specialist task.

What your choice means

Material alone is insufficient. Supply system, seals and supporting assembly; comparison remains a specialist task.

32 of 32 models have candidate records. Sorted by indicative price; verification remains required.

Pyroguard Clear 11mm

Pyroguard · CF257 · 7 candidate records

from £270.18/m²Full details →

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · IGU · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF257 source pages 18, 48, 57, 58 ↗ · extract not independently rechecked

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF257 source pages 6, 7, 8, 9, 10, 11, 12, 13, 38, 42, 43 ↗ · extract not independently rechecked

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Timber · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF257 source pages 21, 22, 23, 24, 27, 28, 29, 30, 31, 32, 33, 34, 37, 50, 55, 56 ↗ · extract not independently rechecked

Integrity 60 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door / Screen · Timber · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF257 source pages 25, 26, 41, 51, 52, 53, 54 ↗ · extract not independently rechecked

Integrity 60 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF257 source pages 41 ↗ · extract not independently rechecked

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · IGU · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF257 source pages 14, 15, 16, 44 ↗ · extract not independently rechecked

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF257 source pages 17, 46 ↗ · extract not independently rechecked

Pyroguard Clear 7mm

Pyroguard · CF257 · 7 candidate records

from £270.18/m²Full details →

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door / Screen · Timber / Steel · IGU / Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF257 source pages 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 21, 22, 23, 24, 27, 28, 29, 30, 31, 32, 33, 34, 37, 38, 42, 43, 44, 46, 48, 50, 55, 56, 57, 58 ↗ · extract not independently rechecked

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · IGU · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF257 source pages 14, 15, 16, 44 ↗ · extract not independently rechecked

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Steel · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF257 source pages 19 ↗ · extract not independently rechecked

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF257 source pages 17, 46 ↗ · extract not independently rechecked

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Timber · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF257 source pages 21, 22, 23, 24, 27, 28, 29, 30, 31, 32, 33, 34, 37, 50, 55, 56 ↗ · extract not independently rechecked

Integrity 60 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Timber · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF257 source pages 25, 26, 51, 52, 53, 54 ↗ · extract not independently rechecked

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF257 source pages 6, 7, 8, 9, 10, 11, 12, 13, 38, 42, 43 ↗ · extract not independently rechecked

AGC Flatglass Pyrobelite 10

AGC Flatglass · CF377 · 1 candidate records

from £297.00/m²Full details →

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 13, 14, 18, 26 ↗ · extract not independently rechecked

AGC Flatglass Pyrobelite 12

AGC Flatglass · CF377 · 4 candidate records

from £297.00/m²Full details →

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 16, 19, 24, 25, 33 ↗ · extract not independently rechecked

Integrity 60 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 34, 52, 64 ↗ · extract not independently rechecked

Integrity 60 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 32 ↗ · extract not independently rechecked

Integrity 60 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Timber · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 12, 30, 31 ↗ · extract not independently rechecked

AGC Flatglass Pyrobelite 7 & 9EG (IGUs)

AGC Flatglass · CF377 · 2 candidate records

from £297.00/m²Full details →

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · IGU · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 13, 14, 18 ↗ · extract not independently rechecked

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · IGU · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 16, 19 ↗ · extract not independently rechecked

AGC Flatglass Pyrobelite 7 & 9EG

AGC Flatglass · CF377 · 3 candidate records

from £297.00/m²Full details →

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 16, 19 ↗ · extract not independently rechecked

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Timber · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 7, 8 ↗ · extract not independently rechecked

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 13, 14, 18 ↗ · extract not independently rechecked

Pilkington pyrodur 30-105, 7mm

Pilkington · CF328 · 1 candidate records

from £297.00/m²Full details →

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door / Screen · Timber · IGU / Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF328 source pages 14, 15 ↗ · extract not independently rechecked

Pilkington pyrodur 30-203, 11mm

Pilkington · CF328 · 1 candidate records

from £297.00/m²Full details →

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF328 source pages 20 ↗ · extract not independently rechecked

Pilkington pyrodur 60-20, 13mm

Pilkington · CF328 · 1 candidate records

from £297.00/m²Full details →

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door / Screen · Steel / Timber · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF328 source pages 25, 27, 28 ↗ · extract not independently rechecked

Pilkington pyrodur 60-10, 10MM

Pilkington · CF328 · 1 candidate records

from £549.78/m²Full details →

Integrity 60 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door / Screen · Timber · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF328 source pages 23, 24 ↗ · extract not independently rechecked

Pyroguard 15mm

Pyroguard · CF437 · 9 candidate records

from £627.00/m²Full details →

Integrity 30 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · IGU · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF437 source pages 26, 32, 34 ↗ · extract not independently rechecked

Integrity 30 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Steel · IGU · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF437 source pages 23, 33 ↗ · extract not independently rechecked

Integrity 30 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · IGU · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF437 source pages 31 ↗ · extract not independently rechecked

Integrity 30 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF437 source pages 22 ↗ · extract not independently rechecked

Integrity 30 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF437 source pages 15, 16, 17, 59 ↗ · extract not independently rechecked

Integrity 60 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF437 source pages 54 ↗ · extract not independently rechecked

Integrity 60 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Timber · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF437 source pages 21 ↗ · extract not independently rechecked

Integrity 60 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF437 source pages 24, 25, 27 ↗ · extract not independently rechecked

Integrity 60 min / insulation 60 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Steel · IGU · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF437 source pages 57, 58 ↗ · extract not independently rechecked

Pilkington pyrostop 30-10, 15MM

Pilkington · CF328 · 1 candidate records

from £657.80/m²Full details →

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Aluminium · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF328 source pages 6, 9, 11, 13, 14 ↗ · extract not independently rechecked

Pilkington pyrostop 30-103, 14mm

Pilkington · CF328 · 5 candidate records

from £657.80/m²Full details →

Integrity 30 min / insulation 30 min

BS 476 Part 22:1987 · no automatic E/EW/EI equivalence

Door · Timber · Single · See certificate

Verification needed

54 mm timber doorset; ceramic tape 15 × 3 mm compressed to 2 mm; beads and fixings per CF328 page 30

Door aperture W × H as stated; doorset evidence required · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.
  • Qualified BS 476 integrity/insulation minutes; not an EN 13501 EI classification.
  • Tabulated pairs are conservative screening bounds; no interpolation or rotation is performed.
  • Complete frame, seal and installation evidence must be checked by the project specialist.

CF328 source pages 30 ↗ · revision 2024-10-22; checked 2026-10-02

Integrity 30 min / insulation 30 min

BS 476 Part 22:1987 · no automatic E/EW/EI equivalence

Screen · Timber · Single · See certificate

Verification needed

Softwood frame 33 × 70 mm, density at least 450 kg/m³; ceramic tape and beads per CF328 page 31

Portrait; vertical within ±10° · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.
  • Qualified BS 476 integrity/insulation minutes; not an EN 13501 EI classification.
  • Tabulated pairs are conservative screening bounds; no interpolation or rotation is performed.
  • Complete frame, seal and installation evidence must be checked by the project specialist.

CF328 source pages 31 ↗ · revision 2024-10-22; checked 2026-10-02

Integrity 30 min / insulation 30 min

BS 476 Part 22:1987 · no automatic E/EW/EI equivalence

Screen · Timber · Single · See certificate

Verification needed

Softwood frame 33 × 70 mm, density at least 450 kg/m³; ceramic tape and beads per CF328 page 31

Landscape; vertical within ±10° · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.
  • Qualified BS 476 integrity/insulation minutes; not an EN 13501 EI classification.
  • Tabulated pairs are conservative screening bounds; no interpolation or rotation is performed.
  • Complete frame, seal and installation evidence must be checked by the project specialist.

CF328 source pages 31 ↗ · revision 2024-10-22; checked 2026-10-02

Integrity 30 min / insulation 30 min

BS 476 Part 22:1987 · no automatic E/EW/EI equivalence

Screen · Steel · Single · See certificate

Verification needed

Steel screen with 15 × 2 mm Fibrefrax glazing tape; supporting frame evidence required, CF328 page 32

Portrait; vertical within ±10° · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.
  • Qualified BS 476 integrity/insulation minutes; not an EN 13501 EI classification.
  • Tabulated pairs are conservative screening bounds; no interpolation or rotation is performed.
  • Complete frame, seal and installation evidence must be checked by the project specialist.

CF328 source pages 32 ↗ · revision 2024-10-22; checked 2026-10-02

Integrity 30 min / insulation 30 min

BS 476 Part 22:1987 · no automatic E/EW/EI equivalence

Screen · Steel · Single · See certificate

Verification needed

Steel screen with 15 × 2 mm Fibrefrax glazing tape; supporting frame evidence required, CF328 page 32

Landscape; vertical within ±10° · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.
  • Qualified BS 476 integrity/insulation minutes; not an EN 13501 EI classification.
  • Tabulated pairs are conservative screening bounds; no interpolation or rotation is performed.
  • Complete frame, seal and installation evidence must be checked by the project specialist.

CF328 source pages 32 ↗ · revision 2024-10-22; checked 2026-10-02

Pilkington pyrostop 30-20, 18mm

Pilkington · CF328 · 1 candidate records

from £657.80/m²Full details →

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Aluminium · Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF328 source pages 16, 19 ↗ · extract not independently rechecked

AGC Flatglass Pyrobel 16 & 16EG (DGUs)

AGC Flatglass · CF377 · 1 candidate records

from £679.14/m²Full details →

Integrity 30 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Steel · IGU · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 36, 37, 38 ↗ · extract not independently rechecked

AGC Flatglass Pyrobel 16 & 16EG (IGUs)

AGC Flatglass · CF377 · 2 candidate records

from £679.14/m²Full details →

Integrity 30 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · IGU · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 49, 54 ↗ · extract not independently rechecked

Integrity 30 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · IGU · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 40, 48 ↗ · extract not independently rechecked

AGC Flatglass Pyrobel 16 & 16EG (Timber Screens)

AGC Flatglass · CF377 · 1 candidate records

from £679.14/m²Full details →

Integrity 30 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 40, 48 ↗ · extract not independently rechecked

AGC Flatglass Pyrobel 16 & 16EG

AGC Flatglass · CF377 · 4 candidate records

from £679.14/m²Full details →

Integrity 30 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 49, 54 ↗ · extract not independently rechecked

Integrity 60 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 35 ↗ · extract not independently rechecked

Integrity 30 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Timber · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 36, 37, 38 ↗ · extract not independently rechecked

Integrity 60 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 39, 41 ↗ · extract not independently rechecked

AGC Flatglass Pyrobel 16

AGC Flatglass · CF377 · 2 candidate records

from £679.14/m²Full details →

Integrity 60 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 34, 52, 64 ↗ · extract not independently rechecked

Integrity 60 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 53, 63 ↗ · extract not independently rechecked

AGC Flatglass Pyrobel 17N

AGC Flatglass · CF377 · 4 candidate records

from £679.14/m²Full details →

Integrity 60 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 39, 41, 62 ↗ · extract not independently rechecked

Integrity 60 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 53, 63 ↗ · extract not independently rechecked

Integrity 60 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Aluminium · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 65 ↗ · extract not independently rechecked

Integrity 60 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 34, 52, 64 ↗ · extract not independently rechecked

AGC Flatglass Pyrobel 30, 30EG & 30DGU

AGC Flatglass · CF377 · 1 candidate records

from £679.14/m²Full details →

Integrity 90 min / insulation 90 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door / Screen · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 86, 87, 88 ↗ · extract not independently rechecked

AGC Flatglass Pyrobel 53, 53N EG

AGC Flatglass · CF377 · 1 candidate records

from £679.14/m²Full details →

Integrity 120 min / insulation 120 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 89 ↗ · extract not independently rechecked

AGC Flatglass Pyrobel Clearvision 16

AGC Flatglass · CF377 · 1 candidate records

from £679.14/m²Full details →

Integrity 60 min / insulation 30 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 53, 63 ↗ · extract not independently rechecked

Pyroguard 23mm

Pyroguard · CF437 · 6 candidate records

from £1089.00/m²Full details →

Integrity 60 min / insulation 60 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · IGU · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF437 source pages 47, 48, 50 ↗ · extract not independently rechecked

Integrity 60 min / insulation 60 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · IGU · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF437 source pages 41, 46 ↗ · extract not independently rechecked

Integrity 60 min / insulation 60 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF437 source pages 49, 55, 56 ↗ · extract not independently rechecked

Integrity 60 min / insulation 60 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF437 source pages 45, 61 ↗ · extract not independently rechecked

Integrity 60 min / insulation 60 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Timber · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF437 source pages 42, 43, 44 ↗ · extract not independently rechecked

Integrity 60 min / insulation 60 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 19 Feb 2031; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF437 source pages 35, 36, 37, 38, 39, 40 ↗ · extract not independently rechecked

Pilkington pyrostop 60-101, 23mm

Pilkington · CF328 · 3 candidate records

from £1111.00/m²Full details →

Integrity 60 min / insulation 60 min

BS 476 Part 22:1987 · no automatic E/EW/EI equivalence

Screen · Timber · Single · See certificate

Verification needed

Hardwood frame 95 × 45 mm, density at least 640 kg/m³; 20 × 2 mm Interdens; beads/fixings per CF328 page 49

Vertical screen, within ±10°; preserve stated W × H orientation · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.
  • Qualified BS 476 integrity/insulation minutes; not an EN 13501 EI classification.
  • Tabulated pairs are conservative screening bounds; no interpolation or rotation is performed.
  • Complete frame, seal and installation evidence must be checked by the project specialist.

CF328 source pages 49 ↗ · revision 2024-10-22; checked 2026-10-02

Integrity 60 min / insulation 60 min

BS 476 Part 22:1987 · no automatic E/EW/EI equivalence

Screen · Steel · Single · See certificate

Verification needed

Previously tested or Certifire approved insulated steel framing; 15 × 2 mm Fibrefrax; aperture evidence required, CF328 page 50

Vertical screen, within ±10°; preserve stated W × H orientation · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.
  • Qualified BS 476 integrity/insulation minutes; not an EN 13501 EI classification.
  • Tabulated pairs are conservative screening bounds; no interpolation or rotation is performed.
  • Complete frame, seal and installation evidence must be checked by the project specialist.

CF328 source pages 50 ↗ · revision 2024-10-22; checked 2026-10-02

Integrity 60 min / insulation 60 min

BS 476 Part 22:1987 · no automatic E/EW/EI equivalence

Door · Steel · Single · See certificate

Verification needed

Fully insulated steel doorset with aperture evidence; 12 × 6 mm Fibrefrax, CF328 page 51

Door aperture W × H as stated; fully insulated doorset evidence required · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.
  • Qualified BS 476 integrity/insulation minutes; not an EN 13501 EI classification.
  • Tabulated pairs are conservative screening bounds; no interpolation or rotation is performed.
  • Complete frame, seal and installation evidence must be checked by the project specialist.

CF328 source pages 51 ↗ · revision 2024-10-22; checked 2026-10-02

Pilkington pyrostop 60-201, 27mm

Pilkington · CF328 · 3 candidate records

from £1111.00/m²Full details →

Integrity 60 min / insulation 60 min

BS 476 Part 22:1987 · no automatic E/EW/EI equivalence

Screen · Timber · Single · See certificate

Verification needed

Hardwood frame 95 × 45 mm, density at least 640 kg/m³; 20 × 2 mm Interdens; beads/fixings per CF328 page 49

Vertical screen, within ±10°; preserve stated W × H orientation · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.
  • Qualified BS 476 integrity/insulation minutes; not an EN 13501 EI classification.
  • Tabulated pairs are conservative screening bounds; no interpolation or rotation is performed.
  • Complete frame, seal and installation evidence must be checked by the project specialist.

CF328 source pages 49 ↗ · revision 2024-10-22; checked 2026-10-02

Integrity 60 min / insulation 60 min

BS 476 Part 22:1987 · no automatic E/EW/EI equivalence

Screen · Steel · Single · See certificate

Verification needed

Previously tested or Certifire approved insulated steel framing; 15 × 2 mm Fibrefrax; aperture evidence required, CF328 page 50

Vertical screen, within ±10°; preserve stated W × H orientation · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.
  • Qualified BS 476 integrity/insulation minutes; not an EN 13501 EI classification.
  • Tabulated pairs are conservative screening bounds; no interpolation or rotation is performed.
  • Complete frame, seal and installation evidence must be checked by the project specialist.

CF328 source pages 50 ↗ · revision 2024-10-22; checked 2026-10-02

Integrity 60 min / insulation 60 min

BS 476 Part 22:1987 · no automatic E/EW/EI equivalence

Door · Steel · Single · See certificate

Verification needed

Fully insulated steel doorset with aperture evidence; 12 × 6 mm Fibrefrax, CF328 page 51

Door aperture W × H as stated; fully insulated doorset evidence required · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).

Within stated validity to 22 Oct 2029; issuer status still requires checking

Conditions and outstanding checks
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.
  • Qualified BS 476 integrity/insulation minutes; not an EN 13501 EI classification.
  • Tabulated pairs are conservative screening bounds; no interpolation or rotation is performed.
  • Complete frame, seal and installation evidence must be checked by the project specialist.

CF328 source pages 51 ↗ · revision 2024-10-22; checked 2026-10-02

AGC Flatglass Pyrobel 25-25DGU

AGC Flatglass · CF377 · 1 candidate records

from £1155.00/m²Full details →

Integrity 120 min / insulation 120 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 89, 91, 92, 93, 96 ↗ · extract not independently rechecked

AGC Flatglass Pyrobel 25 & 25EG (IGUs)

AGC Flatglass · CF377 · 3 candidate records

from £1155.00/m²Full details →

Integrity 60 min / insulation 60 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 72, 73 ↗ · extract not independently rechecked

Integrity 60 min / insulation 60 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · IGU · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 70, 71, 75 ↗ · extract not independently rechecked

Integrity 60 min / insulation 60 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · IGU · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 67, 68, 69 ↗ · extract not independently rechecked

AGC Flatglass Pyrobel 25 & 25EG

AGC Flatglass · CF377 · 4 candidate records

from £1155.00/m²Full details →

Integrity 60 min / insulation 60 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 72, 73 ↗ · extract not independently rechecked

Integrity 60 min / insulation 60 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Steel · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 70, 71, 75 ↗ · extract not independently rechecked

Integrity 60 min / insulation 60 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door · Timber · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 66 ↗ · extract not independently rechecked

Integrity 60 min / insulation 60 min

Test regime requires verification · no automatic E/EW/EI equivalence

Screen · Timber · Single · Internal or External

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Within stated validity to 20 Jun 2029; issuer status still requires checking

Conditions and outstanding checks
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF377 source pages 67, 68, 69 ↗ · extract not independently rechecked

Pyroguard EW30/11-2

Pyroguard · CF5818 · 1 candidate records

Price on requestFull details →

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door / Screen · Timber / Steel · IGU · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Expired 8 Oct 2026 — renewed evidence required

Conditions and outstanding checks
  • Expired 8 Oct 2026 — renewed evidence required
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF5818 source pages 14, 36, 37, 58, 59, 63, 66, 68 ↗ · extract not independently rechecked

Pyroguard EW30/7-1

Pyroguard · CF5818 · 1 candidate records

Price on requestFull details →

Integrity 30 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door / Screen · Timber / Steel · IGU / Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Expired 8 Oct 2026 — renewed evidence required

Conditions and outstanding checks
  • Expired 8 Oct 2026 — renewed evidence required
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF5818 source pages 7, 8, 9, 10, 11, 12, 13, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 56, 57, 62 ↗ · extract not independently rechecked

Pyroguard EW60/11-2

Pyroguard · CF5818 · 1 candidate records

Price on requestFull details →

Integrity 60 min / insulation 0 min

Test regime requires verification · no automatic E/EW/EI equivalence

Door / Screen · Steel / Timber · IGU / Single · Internal

Verification needed

Exact construction requires certificate review

Orientation unverified · Fire direction unverified

Expired 8 Oct 2026 — renewed evidence required

Conditions and outstanding checks
  • Expired 8 Oct 2026 — renewed evidence required
  • Extracted technical record has not been checked against the current system certificate.
  • Internal/external suitability must be confirmed.
  • Exact framing/glazing system has not been supplied.
  • Orientation and fire exposure direction require confirmation.
  • Enter width and height; area alone cannot verify aperture limits.
  • Project specialist must check all frame, seal, fixing, supporting assembly and exposure conditions.

CF5818 source pages 16, 17, 18, 19, 38, 39, 40, 41, 42, 43, 44, 45, 46, 47, 48, 49, 50, 51, 52, 60, 61, 64, 67, 69 ↗ · extract not independently rechecked

Fire glass by manufacturer

Manufacturer information and recorded product ranges. Each project needs current, complete-system evidence; browsing a product does not qualify an installation.

Source certificates

Warringtonfire Testing and Certification (Certifire scheme, Technical Schedule TS25). Fire-resisting glass must only be used in an approved glazing system.

CertScopeHolderReissued / revisedValid toDownload
CF437Pyroguard EI (INT/EXT)Pyroguard UK Ltd10 Feb 202619 Feb 2031

Within stated validity to 19 Feb 2031; issuer status still requires checking

PDF ↗
CF257Pyroguard EW (verify radiation classification)Pyroguard UK Ltd16 Dec 202519 Feb 2031

Within stated validity to 19 Feb 2031; issuer status still requires checking

PDF ↗
CF377AGC Pyrobel / Pyrobelite (EG = external)AGC Glass UK Ltd6 Aug 202420 Jun 2029

Within stated validity to 20 Jun 2029; issuer status still requires checking

PDF ↗
CF328Pilkington Pyrodur / PyrostopPilkington UK Ltd22 Oct 202422 Oct 2029

Within stated validity to 22 Oct 2029; issuer status still requires checking

PDF ↗
CF5818Pyroguard Advance 2-EW/2-FD/2-EIPyroguard UK Ltd16 Sep 2025 (rev)8 Oct 2026

Expired 8 Oct 2026 — renewed evidence required

PDF ↗

Status is evaluated against the stated validity date. Verify issuer status, current revision, test regime and every system limitation before use. An unexpired document does not independently establish suitability for your project.