Pilkington pyrostop 30-103, 14mm
Pilkington · evidence reference CF328 (Warringtonfire Certifire, stated validity to 22 Oct 2029)
Within stated validity to 22 Oct 2029; issuer status still requires checking
This glass can achieve different fire ratings depending on how it is used — internal or external, door or screen, single or double-glazed unit, and the framing system. Each record below must be checked against the current certificate, test regime and complete framing, seals, fixings, installation and exposure. Only explicitly reviewed mappings carry review provenance; other extracted data remains unverified.
Request a quote for this glass
Give us your size and contact details and verified local suppliers will quote — no account needed, just an email to confirm.
Certified options for this glass
Check recorded size bounds and outstanding evidence
A size fit is only one part of qualification. The complete framing, seals, fixings, exposure and current certificate must be checked. No rotation or interpolation between tabulated pairs is assumed.
System verification required
BS 476 Part 22:1987 · numeric integrity/insulation minutes do not automatically establish EN 13501 E/EW/EI.
Within stated validity to 22 Oct 2029; issuer status still requires checking
54 mm timber doorset; ceramic tape 15 × 3 mm compressed to 2 mm; beads and fixings per CF328 page 30
Door aperture W × H as stated; doorset evidence required · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).
Reviewed source pages 30 · revision 2024-10-22 · checked 2026-10-02 ↗Door
Timber
Single
See certificate
1.56 m² max area · 856 × 2243 mmtested pairs: 696×2243, 856×1824
Confirm the cited system's width, height, area, orientation and any dimension graph; do not assume rotation or interpolation.
- 54 mm timber doorset; ceramic tape 15 × 3 mm compressed to 2 mm; beads and fixings per CF328 page 30
- Read the cited system page together with CF328 general conditions, pages 3–5. Verify beads, fixing centres, seals, aperture and supporting assembly.
System verification required
BS 476 Part 22:1987 · numeric integrity/insulation minutes do not automatically establish EN 13501 E/EW/EI.
Within stated validity to 22 Oct 2029; issuer status still requires checking
Softwood frame 33 × 70 mm, density at least 450 kg/m³; ceramic tape and beads per CF328 page 31
Portrait; vertical within ±10° · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).
Reviewed source pages 31 · revision 2024-10-22 · checked 2026-10-02 ↗Screen
Timber
Single
See certificate
2.2 m² max area · 1000 × 2200 mmtested pairs: 1000×2200
Confirm the cited system's width, height, area, orientation and any dimension graph; do not assume rotation or interpolation.
- Softwood frame 33 × 70 mm, density at least 450 kg/m³; ceramic tape and beads per CF328 page 31
- Read the cited system page together with CF328 general conditions, pages 3–5. Verify beads, fixing centres, seals, aperture and supporting assembly.
System verification required
BS 476 Part 22:1987 · numeric integrity/insulation minutes do not automatically establish EN 13501 E/EW/EI.
Within stated validity to 22 Oct 2029; issuer status still requires checking
Softwood frame 33 × 70 mm, density at least 450 kg/m³; ceramic tape and beads per CF328 page 31
Landscape; vertical within ±10° · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).
Reviewed source pages 31 · revision 2024-10-22 · checked 2026-10-02 ↗Screen
Timber
Single
See certificate
1.82 m² max area · 2323 × 961 mmtested pairs: 1889×961, 2323×781
Confirm the cited system's width, height, area, orientation and any dimension graph; do not assume rotation or interpolation.
- Softwood frame 33 × 70 mm, density at least 450 kg/m³; ceramic tape and beads per CF328 page 31
- Read the cited system page together with CF328 general conditions, pages 3–5. Verify beads, fixing centres, seals, aperture and supporting assembly.
System verification required
BS 476 Part 22:1987 · numeric integrity/insulation minutes do not automatically establish EN 13501 E/EW/EI.
Within stated validity to 22 Oct 2029; issuer status still requires checking
Steel screen with 15 × 2 mm Fibrefrax glazing tape; supporting frame evidence required, CF328 page 32
Portrait; vertical within ±10° · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).
Reviewed source pages 32 · revision 2024-10-22 · checked 2026-10-02 ↗Screen
Steel
Single
See certificate
2.2 m² max area · 1000 × 2200 mmtested pairs: 1000×2200
Confirm the cited system's width, height, area, orientation and any dimension graph; do not assume rotation or interpolation.
- Steel screen with 15 × 2 mm Fibrefrax glazing tape; supporting frame evidence required, CF328 page 32
- Read the cited system page together with CF328 general conditions, pages 3–5. Verify beads, fixing centres, seals, aperture and supporting assembly.
System verification required
BS 476 Part 22:1987 · numeric integrity/insulation minutes do not automatically establish EN 13501 E/EW/EI.
Within stated validity to 22 Oct 2029; issuer status still requires checking
Steel screen with 15 × 2 mm Fibrefrax glazing tape; supporting frame evidence required, CF328 page 32
Landscape; vertical within ±10° · Check complete-system exposure restrictions; glass alone has no general direction restriction (page 4).
Reviewed source pages 32 · revision 2024-10-22 · checked 2026-10-02 ↗Screen
Steel
Single
See certificate
1.82 m² max area · 2323 × 961 mmtested pairs: 1889×961, 2323×781
Confirm the cited system's width, height, area, orientation and any dimension graph; do not assume rotation or interpolation.
- Steel screen with 15 × 2 mm Fibrefrax glazing tape; supporting frame evidence required, CF328 page 32
- Read the cited system page together with CF328 general conditions, pages 3–5. Verify beads, fixing centres, seals, aperture and supporting assembly.
Understanding the grades
Integrity for the classified duration. It does not establish radiation control or insulation.
The complete system and classification report determine E performance.
Integrity plus a radiation limit for the classified duration. EW is distinct from E and from EI.
Check radiation performance in the system classification report.
Integrity plus insulation for the classified duration. A BS 476 integrity/insulation pair alone is not an EN 13501 EI classification.
Specify class and minutes from the project fire strategy.
Manufacturer location/exposure terminology, separate from fire-resistance class. Confirm the specific glass, system and installation conditions.
Internal/external suitability cannot be inferred from the letters E, EW or EI.